Empower Lubricant

Transformer Oils

Empower TRANSFORMER OIL is designed for human safety and free from carcinogenic Poly chlorinated Bi-phenyls (PCB) and Poly aromatic hydrocarbon (PAH).

PROPOSED USAGE

  • Electric transformers
  • Switch gears
  • Circuit breakers which require insulating fluids
  • Has very high oxidation stability
  • Excellent ageing properties resulting in long product life

Our product conforms to IEC 60296:2003/BS-148:1998

Note:

  • 1. The above data is indicative of recent average values only. Minor variations which do not affect product performance or quality may be expected in manufacture.
  • 2. Specific requirements can be custom-made on request.
TEST DESCRIPTION TEST METHOD       SPECIFICATION LIMITS TYPICAL VALUES
Appearance BS 148-1998 Transparent, clear, bright, odourless liquid free from suspended impurities Transparent, clear, bright, odourless liquid free from suspended impurities
Colour ASTM D 1500 L 0.5 0.5
Kinematic Viscosity, mm2/S (max)
At 40°C ISO 3104 11 9.0
At -30°C ISO 3104 1800 298
Flash Point °C,(Min), PMCC ISO 2719 130 150
Pour Point °C ISO 3016 ≤ – 45 -45
Density kg/dm3, @ 20°C (Max) BS EN ISO 3675 0.895 0.88
Neutralisation Value mg KOH/g (Max) IEC – 62021 0.01 Nil
Interfacial Tension @ 25°C ISO – 6295 0.04 Max 0.045
Corrosive Sulphur DIN 51353/BS 5680 Non corrosive Non corrosive
Water Content, Max mg/kg IEC 60814
a) Bulk 20 14
b) Drum 30 22
Anti – oxidant Additives (Sub Clause 2.5) IEC 60666/BS 5984 Not detectable Not detectable
Oxidation Stability, 164 h
Total acidity, mg KOH/g of oil (Max)
Sludge, % by mass (Max)
DDF @ 90°C
IEC 61125 : 1993
(Method C)
IEC – 60247
1.2
0.8
0.5
1.0
0.68
0.36
Break down Voltage, Min IEC 60156
As Delivered (Kv), min 30 50
After Treatment (Kv), min 70 70
Dielectric Dissipation factor at 90°C and 40 to 60 Hz (Max) IEC – 60247/61620 0.005 0.0005
Gassing tendency at 50 Hz after 120 min, mm3/min Method A (Max) BS 5797/IEC-60628-A +5 +1

Designed & Developed By Digital Media